{"resultsPerPage":1,"startIndex":0,"totalResults":1,"format":"NVD_CVE","version":"2.0","timestamp":"2026-04-27T01:30:28.424","vulnerabilities":[{"cve":{"id":"CVE-2025-7693","sourceIdentifier":"PSIRT@rockwellautomation.com","published":"2025-08-18T18:15:40.573","lastModified":"2026-04-15T00:35:42.020","vulnStatus":"Deferred","cveTags":[],"descriptions":[{"lang":"en","value":"A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault."},{"lang":"es","value":"Existe un problema de seguridad debido al manejo incorrecto de paquetes CIP Forward Close malformados durante el fuzzing. El controlador entra en un estado de fallo rojo fijo y deja de responder. Al reiniciar, el controlador entra en un fallo recuperable donde el LED MS y el LED de fallo parpadean en rojo e informan el código de fallo 0xF015. Para recuperarse, borre el fallo."}],"metrics":{"cvssMetricV40":[{"source":"PSIRT@rockwellautomation.com","type":"Secondary","cvssData":{"version":"4.0","vectorString":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X","baseScore":9.3,"baseSeverity":"CRITICAL","attackVector":"NETWORK","attackComplexity":"LOW","attackRequirements":"NONE","privilegesRequired":"NONE","userInteraction":"NONE","vulnConfidentialityImpact":"HIGH","vulnIntegrityImpact":"HIGH","vulnAvailabilityImpact":"HIGH","subConfidentialityImpact":"NONE","subIntegrityImpact":"NONE","subAvailabilityImpact":"NONE","exploitMaturity":"NOT_DEFINED","confidentialityRequirement":"NOT_DEFINED","integrityRequirement":"NOT_DEFINED","availabilityRequirement":"NOT_DEFINED","modifiedAttackVector":"NOT_DEFINED","modifiedAttackComplexity":"NOT_DEFINED","modifiedAttackRequirements":"NOT_DEFINED","modifiedPrivilegesRequired":"NOT_DEFINED","modifiedUserInteraction":"NOT_DEFINED","modifiedVulnConfidentialityImpact":"NOT_DEFINED","modifiedVulnIntegrityImpact":"NOT_DEFINED","modifiedVulnAvailabilityImpact":"NOT_DEFINED","modifiedSubConfidentialityImpact":"NOT_DEFINED","modifiedSubIntegrityImpact":"NOT_DEFINED","modifiedSubAvailabilityImpact":"NOT_DEFINED","Safety":"NOT_DEFINED","Automatable":"NOT_DEFINED","Recovery":"NOT_DEFINED","valueDensity":"NOT_DEFINED","vulnerabilityResponseEffort":"NOT_DEFINED","providerUrgency":"NOT_DEFINED"}}]},"weaknesses":[{"source":"PSIRT@rockwellautomation.com","type":"Secondary","description":[{"lang":"en","value":"CWE-20"}]}],"references":[{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1736.html","source":"PSIRT@rockwellautomation.com"}]}}]}