{"resultsPerPage":1,"startIndex":0,"totalResults":1,"format":"NVD_CVE","version":"2.0","timestamp":"2026-05-02T03:48:00.658","vulnerabilities":[{"cve":{"id":"CVE-2022-34820","sourceIdentifier":"productcert@siemens.com","published":"2022-07-12T10:15:12.343","lastModified":"2024-11-21T07:10:15.080","vulnStatus":"Modified","cveTags":[],"descriptions":[{"lang":"en","value":"A vulnerability has been identified in SIMATIC CP 1242-7 V2 (All versions < V3.3.46), SIMATIC CP 1243-1 (All versions < V3.3.46), SIMATIC CP 1243-7 LTE EU (All versions < V3.3.46), SIMATIC CP 1243-7 LTE US (All versions < V3.3.46), SIMATIC CP 1243-8 IRC (All versions < V3.3.46), SIMATIC CP 1542SP-1 IRC (All versions >= V2.0 < V2.2.28), SIMATIC CP 1543-1 (All versions < V3.0.22), SIMATIC CP 1543SP-1 (All versions >= V2.0 < V2.2.28), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (All versions >= V2.0 < V2.2.28), SIPLUS ET 200SP CP 1543SP-1 ISEC (All versions >= V2.0 < V2.2.28), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (All versions >= V2.0 < V2.2.28), SIPLUS NET CP 1242-7 V2 (All versions < V3.3.46), SIPLUS NET CP 1543-1 (All versions < V3.0.22), SIPLUS S7-1200 CP 1243-1 (All versions < V3.3.46), SIPLUS S7-1200 CP 1243-1 RAIL (All versions < V3.3.46). The application does not correctly escape some user provided fields during the authentication process. This could allow an attacker to inject custom commands and execute arbitrary code with elevated privileges."},{"lang":"es","value":"Se ha identificado una vulnerabilidad en SIMATIC CP 1242-7 V2 (Todas las versiones anteriores a V3.3.46), SIMATIC CP 1243-1 (Todas las versiones anteriores a V3.3.46), SIMATIC CP 1243-7 LTE EU (Todas las versiones anteriores a V3.3.46), SIMATIC CP 1243-7 LTE US (Todas las versiones anteriores a V3. 3.46), SIMATIC CP 1243-8 IRC (Todas las versiones anteriores a V3.3.46), SIMATIC CP 1542SP-1 IRC (Todas las versiones posteriores o iguales a V2.0), SIMATIC CP 1543-1 (Todas las versiones anteriores a V3.0.22), SIMATIC CP 1543SP-1 (Todas las versiones posteriores o iguales a V2. 0), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (Todas las versiones posteriores o iguales a V2.0), SIPLUS ET 200SP CP 1543SP-1 ISEC (Todas las versiones posteriores o iguales a V2.0), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (Todas las versiones posteriores o iguales a V2. 0), SIPLUS NET CP 1242-7 V2 (Todas las versiones anteriores a V3.3.46), SIPLUS NET CP 1543-1 (Todas las versiones anteriores a V3.0.22), SIPLUS S7-1200 CP 1243-1 (Todas las versiones anteriores a V3.3.46), SIPLUS S7-1200 CP 1243-1 RAIL (Todas las versiones anteriores a V3.3.46). La aplicación no escapa correctamente de algunos campos proporcionados por el usuario durante el proceso de autenticación. Esto podría permitir a un atacante inyectar comandos personalizados y ejecutar código arbitrario con privilegios elevados"}],"metrics":{"cvssMetricV31":[{"source":"productcert@siemens.com","type":"Secondary","cvssData":{"version":"3.1","vectorString":"CVSS:3.1/AV:A/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H","baseScore":8.4,"baseSeverity":"HIGH","attackVector":"ADJACENT_NETWORK","attackComplexity":"LOW","privilegesRequired":"HIGH","userInteraction":"NONE","scope":"CHANGED","confidentialityImpact":"HIGH","integrityImpact":"HIGH","availabilityImpact":"HIGH"},"exploitabilityScore":1.7,"impactScore":6.0},{"source":"nvd@nist.gov","type":"Secondary","cvssData":{"version":"3.1","vectorString":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H","baseScore":9.8,"baseSeverity":"CRITICAL","attackVector":"NETWORK","attackComplexity":"LOW","privilegesRequired":"NONE","userInteraction":"NONE","scope":"UNCHANGED","confidentialityImpact":"HIGH","integrityImpact":"HIGH","availabilityImpact":"HIGH"},"exploitabilityScore":3.9,"impactScore":5.9}],"cvssMetricV2":[{"source":"nvd@nist.gov","type":"Primary","cvssData":{"version":"2.0","vectorString":"AV:N/AC:M/Au:N/C:C/I:C/A:C","baseScore":9.3,"accessVector":"NETWORK","accessComplexity":"MEDIUM","authentication":"NONE","confidentialityImpact":"COMPLETE","integrityImpact":"COMPLETE","availabilityImpact":"COMPLETE"},"baseSeverity":"HIGH","exploitabilityScore":8.6,"impactScore":10.0,"acInsufInfo":false,"obtainAllPrivilege":false,"obtainUserPrivilege":false,"obtainOtherPrivilege":false,"userInteractionRequired":false}]},"weaknesses":[{"source":"productcert@siemens.com","type":"Secondary","description":[{"lang":"en","value":"CWE-77"}]},{"source":"nvd@nist.gov","type":"Primary","description":[{"lang":"en","value":"CWE-116"}]}],"configurations":[{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:simatic_cp_1242-7_v2_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"3.3.46","matchCriteriaId":"1DB5A20B-3FFD-46DE-A838-D5121AD8CA05"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:simatic_cp_1242-7_v2:-:*:*:*:*:*:*:*","matchCriteriaId":"29D4C72C-4E84-4563-9D66-5C641AB996BA"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:simatic_cp_1243-1_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"3.3.46","matchCriteriaId":"E20882A0-3D80-45C0-BB83-A064A5D27483"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:simatic_cp_1243-1:-:*:*:*:*:*:*:*","matchCriteriaId":"CA9BB25C-D5E3-43DE-8C73-06BDC43CA960"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:simatic_cp_1243-7_lte_eu_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"3.3.46","matchCriteriaId":"6F0F009F-A744-40E7-910E-2789BF16648D"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:simatic_cp_1243-7_lte_eu:-:*:*:*:*:*:*:*","matchCriteriaId":"651C66E8-B3C0-4E88-BC7C-30BF16A7F7A3"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:simatic_cp_1243-7_lte_us_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"3.3.46","matchCriteriaId":"80C6BD76-99C6-4D27-9CCA-ED0915DEFB5B"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:simatic_cp_1243-7_lte_us:-:*:*:*:*:*:*:*","matchCriteriaId":"FF9224A6-8A35-4F4F-951F-5B24B89E5FC8"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:simatic_cp_1243-8_irc_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"3.3.46","matchCriteriaId":"BA4FF14E-2CDA-4A28-BB9E-217AD3C808DB"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:simatic_cp_1243-8_irc:-:*:*:*:*:*:*:*","matchCriteriaId":"12A45F37-1E7D-4748-ADAC-EC4C454B693A"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:simatic_cp_1542sp-1_irc_firmware:*:*:*:*:*:*:*:*","versionStartIncluding":"2.0","versionEndExcluding":"2.2.28","matchCriteriaId":"5F6C0C17-BDD5-4503-9D8C-3143C6074705"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:simatic_cp_1542sp-1_irc:-:*:*:*:*:*:*:*","matchCriteriaId":"E362CEA5-F47B-4294-8F2D-A0A7AC6FF390"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:simatic_cp_1543-1_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"3.0.22","matchCriteriaId":"BFC6ACFD-8893-4EA3-976B-FAAF7240C5DB"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:simatic_cp_1543-1:-:*:*:*:*:*:*:*","matchCriteriaId":"3FDE92FB-38C7-46E8-9208-BBD7872219D5"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:simatic_cp_1543sp-1_firmware:*:*:*:*:*:*:*:*","versionStartIncluding":"2.0","versionEndExcluding":"2.2.28","matchCriteriaId":"EE0A05A9-E1E0-475F-953D-61AC673BF3C4"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:simatic_cp_1543sp-1:-:*:*:*:*:*:*:*","matchCriteriaId":"843A8686-5172-4782-BB97-B5D3C6FB27A3"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:siplus_et_200sp_cp_1542sp-1_irc_tx_rail_firmware:*:*:*:*:*:*:*:*","versionStartIncluding":"2.0","versionEndExcluding":"2.2.28","matchCriteriaId":"B815C6C6-FDE0-404A-8492-27519909A6C3"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:siplus_et_200sp_cp_1542sp-1_irc_tx_rail:-:*:*:*:*:*:*:*","matchCriteriaId":"FF3E5DDA-1BD4-4511-A2C8-4B5D40E6755E"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:siplus_et_200sp_cp_1543sp-1_isec_firmware:*:*:*:*:*:*:*:*","versionStartIncluding":"2.0","versionEndExcluding":"2.2.28","matchCriteriaId":"9B1C1F68-AE3D-47EB-9370-B2FE3F07C3C2"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:siplus_et_200sp_cp_1543sp-1_isec:-:*:*:*:*:*:*:*","matchCriteriaId":"A60FC550-A518-46BF-9124-E21DD654981C"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:siplus_et_200sp_cp_1543sp-1_isec_tx_rail_firmware:*:*:*:*:*:*:*:*","versionStartIncluding":"2.0","versionEndExcluding":"2.2.28","matchCriteriaId":"3ED5D3BC-ABD7-493D-8998-C1B5F17B3C24"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:siplus_et_200sp_cp_1543sp-1_isec_tx_rail:-:*:*:*:*:*:*:*","matchCriteriaId":"25634AD2-2CC0-45AF-B5DE-39D30CBA91A4"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:siplus_net_cp_1242-7_v2_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"3.3.46","matchCriteriaId":"7FD90115-FA81-4880-B05B-0FEA9FA51C71"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:siplus_net_cp_1242-7_v2:-:*:*:*:*:*:*:*","matchCriteriaId":"116E84DA-31F7-4AAC-A1AE-491C4C98BD49"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:siplus_net_cp_1543-1_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"3.0.22","matchCriteriaId":"43CDCCE3-B8C0-44D4-A8A0-25C49A4EA240"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:siplus_net_cp_1543-1:-:*:*:*:*:*:*:*","matchCriteriaId":"5D7AB0D5-FD3E-416A-975B-D212B3350433"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:siplus_s7-1200_cp_1243-1_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"3.3.46","matchCriteriaId":"27851880-F35C-495E-8DFF-CB3D03CED376"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:siplus_s7-1200_cp_1243-1:-:*:*:*:*:*:*:*","matchCriteriaId":"F9E746CF-4009-4A14-8916-A9E0276CAF8B"}]}]},{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:siemens:siplus_s7-1200_cp_1243-1_rail_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"3.3.46","matchCriteriaId":"E0C64F3D-FEBC-4AB4-9FCF-19B59F9BF5A3"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:siemens:siplus_s7-1200_cp_1243-1_rail:-:*:*:*:*:*:*:*","matchCriteriaId":"4A294530-727C-4535-8B02-668DF74587D4"}]}]}],"references":[{"url":"https://cert-portal.siemens.com/productcert/pdf/ssa-517377.pdf","source":"productcert@siemens.com","tags":["Patch","Vendor Advisory"]},{"url":"https://cert-portal.siemens.com/productcert/pdf/ssa-517377.pdf","source":"af854a3a-2127-422b-91ae-364da2661108","tags":["Patch","Vendor Advisory"]}]}}]}