{"resultsPerPage":1,"startIndex":0,"totalResults":1,"format":"NVD_CVE","version":"2.0","timestamp":"2026-04-19T12:14:41.423","vulnerabilities":[{"cve":{"id":"CVE-2021-22823","sourceIdentifier":"cybersecurity@se.com","published":"2022-02-11T18:15:09.570","lastModified":"2024-11-21T05:50:44.777","vulnStatus":"Modified","cveTags":[],"descriptions":[{"lang":"en","value":"A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause deletion of arbitrary files in the context of the user running IGSS due to lack of validation of network messages. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21320 and prior)"},{"lang":"es","value":"Una CWE-306: Se presenta una vulnerabilidad de Falta de Autenticación para una Función Crítica que podría causar el borrado de archivos arbitrarios en el contexto del usuario que ejecuta IGSS debido a una falta de comprobación de los mensajes de red. Producto afectado: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21320 y anteriores)"}],"metrics":{"cvssMetricV31":[{"source":"nvd@nist.gov","type":"Primary","cvssData":{"version":"3.1","vectorString":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H","baseScore":9.1,"baseSeverity":"CRITICAL","attackVector":"NETWORK","attackComplexity":"LOW","privilegesRequired":"NONE","userInteraction":"NONE","scope":"UNCHANGED","confidentialityImpact":"NONE","integrityImpact":"HIGH","availabilityImpact":"HIGH"},"exploitabilityScore":3.9,"impactScore":5.2}],"cvssMetricV2":[{"source":"nvd@nist.gov","type":"Primary","cvssData":{"version":"2.0","vectorString":"AV:N/AC:L/Au:N/C:N/I:P/A:N","baseScore":5.0,"accessVector":"NETWORK","accessComplexity":"LOW","authentication":"NONE","confidentialityImpact":"NONE","integrityImpact":"PARTIAL","availabilityImpact":"NONE"},"baseSeverity":"MEDIUM","exploitabilityScore":10.0,"impactScore":2.9,"acInsufInfo":false,"obtainAllPrivilege":false,"obtainUserPrivilege":false,"obtainOtherPrivilege":false,"userInteractionRequired":false}]},"weaknesses":[{"source":"cybersecurity@se.com","type":"Secondary","description":[{"lang":"en","value":"CWE-306"}]}],"configurations":[{"nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:a:schneider-electric:interactive_graphical_scada_system_data_collector:*:*:*:*:*:*:*:*","versionEndIncluding":"15.0.0.21320","matchCriteriaId":"BCC36B69-9234-4136-8A41-4AF378DD9842"}]}]}],"references":[{"url":"https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-348-01","source":"cybersecurity@se.com","tags":["Patch","Vendor Advisory"]},{"url":"https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-348-01","source":"af854a3a-2127-422b-91ae-364da2661108","tags":["Patch","Vendor Advisory"]}]}}]}