{"resultsPerPage":1,"startIndex":0,"totalResults":1,"format":"NVD_CVE","version":"2.0","timestamp":"2026-04-23T09:15:36.475","vulnerabilities":[{"cve":{"id":"CVE-2018-7246","sourceIdentifier":"cybersecurity@se.com","published":"2018-04-18T20:29:00.577","lastModified":"2024-11-21T04:11:52.270","vulnStatus":"Modified","cveTags":[],"descriptions":[{"lang":"en","value":"A cleartext transmission of sensitive information vulnerability exists in Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. he integrated web server (Port 80/443/TCP) of the affected devices could allow remote attackers to discover an administrative account. If default on device, it is not using a SSL in settings and if multiple request of the page \"Access Control\" (IP-address device/ups/pas_cont.htm) account data will be sent in cleartext"},{"lang":"es","value":"Existe una vulnerabilidad de transmisión en texto claro de información sensible en 66074 MGE Network Management Card Transverse, de Schneider Electric, instalado en MGE UPS y MGE STS. El servidor web integrado (Puerto 80/443/TCP) de los dispositivos afectados podría permitir que atacantes remotos descubran una cuenta administrativa. Por defecto, si en el dispositivo no se emplea SSL en las opciones y si hay múltiples peticiones de la página \"Access Control\" (IP-address device/ups/pas_cont.htm), los datos de la cuenta se enviarán en texto claro."}],"metrics":{"cvssMetricV30":[{"source":"nvd@nist.gov","type":"Primary","cvssData":{"version":"3.0","vectorString":"CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H","baseScore":9.8,"baseSeverity":"CRITICAL","attackVector":"NETWORK","attackComplexity":"LOW","privilegesRequired":"NONE","userInteraction":"NONE","scope":"UNCHANGED","confidentialityImpact":"HIGH","integrityImpact":"HIGH","availabilityImpact":"HIGH"},"exploitabilityScore":3.9,"impactScore":5.9}],"cvssMetricV2":[{"source":"nvd@nist.gov","type":"Primary","cvssData":{"version":"2.0","vectorString":"AV:N/AC:L/Au:N/C:P/I:N/A:N","baseScore":5.0,"accessVector":"NETWORK","accessComplexity":"LOW","authentication":"NONE","confidentialityImpact":"PARTIAL","integrityImpact":"NONE","availabilityImpact":"NONE"},"baseSeverity":"MEDIUM","exploitabilityScore":10.0,"impactScore":2.9,"acInsufInfo":true,"obtainAllPrivilege":false,"obtainUserPrivilege":false,"obtainOtherPrivilege":false,"userInteractionRequired":false}]},"weaknesses":[{"source":"nvd@nist.gov","type":"Primary","description":[{"lang":"en","value":"CWE-319"}]}],"configurations":[{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:h:schneider-electric:66074_mge_network_management_card_transverse:-:*:*:*:*:*:*:*","matchCriteriaId":"7DBB8697-64F8-4D15-8B14-CDD51E99FBCF"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:mge_comet_ups:-:*:*:*:*:*:*:*","matchCriteriaId":"F9837318-C9B6-448E-B701-40929C96795A"},{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:mge_eps_6000:-:*:*:*:*:*:*:*","matchCriteriaId":"98078458-B5AB-4AD2-9E57-390591469F37"},{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:mge_eps_7000:-:*:*:*:*:*:*:*","matchCriteriaId":"05DE2424-0969-491D-A414-81A648F2F801"},{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:mge_eps_8000:-:*:*:*:*:*:*:*","matchCriteriaId":"60DC5EF0-1929-4D67-89BF-47D6F6848411"},{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:mge_galaxy_3000:-:*:*:*:*:*:*:*","matchCriteriaId":"955C94DD-90E6-4AB1-87CC-4EDACEA47DF0"},{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:mge_galaxy_4000:-:*:*:*:*:*:*:*","matchCriteriaId":"7FCAE877-B3E9-4970-B0EE-49C64C85715C"},{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:mge_galaxy_5000:-:*:*:*:*:*:*:*","matchCriteriaId":"4EBFA4F2-6574-4D58-9B0C-317229DF503E"},{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:mge_galaxy_6000:-:*:*:*:*:*:*:*","matchCriteriaId":"790BF7D0-4E2D-4607-8C47-C4B707538E66"},{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:mge_galaxy_9000:-:*:*:*:*:*:*:*","matchCriteriaId":"54A1FC87-5319-4F69-9228-C664D505B1CC"},{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:mge_galaxy_pw:-:*:*:*:*:*:*:*","matchCriteriaId":"59D9633E-051F-427A-BADA-61BC8501AAE9"}]}]}],"references":[{"url":"https://www.schneider-electric.com/en/download/document/SEVD-2018-074-01/","source":"cybersecurity@se.com","tags":["Mitigation","Vendor Advisory"]},{"url":"https://www.schneider-electric.com/en/download/document/SEVD-2018-074-01/","source":"af854a3a-2127-422b-91ae-364da2661108","tags":["Mitigation","Vendor Advisory"]}]}}]}