{"resultsPerPage":1,"startIndex":0,"totalResults":1,"format":"NVD_CVE","version":"2.0","timestamp":"2026-05-01T13:03:59.745","vulnerabilities":[{"cve":{"id":"CVE-2016-8352","sourceIdentifier":"ics-cert@hq.dhs.gov","published":"2017-02-13T21:59:00.767","lastModified":"2025-04-20T01:37:25.860","vulnStatus":"Deferred","cveTags":[],"descriptions":[{"lang":"en","value":"An issue was discovered in Schneider Electric ConneXium firewalls TCSEFEC23F3F20 all versions, TCSEFEC23F3F21 all versions, TCSEFEC23FCF20 all versions, TCSEFEC23FCF21 all versions, and TCSEFEC2CF3F20 all versions. A stack-based buffer overflow can be triggered during the SNMP login authentication process that may allow an attacker to remotely execute code."},{"lang":"es","value":"Ha sido descubierto un problema en los cortafuegos Schneider Electric ConneXium TCSEFEC23F3F20 todas las versiones, TCSEFEC23F3F21 todas las versiones, TCSEFEC23FCF20 todas las versiones, TCSEFEC23FCF21 todas las versiones, y TCSEFEC2CF3F20 todas las versiones. Un desbordamiento de búfer basado en pila puede ser desencadenado durante el proceso de autenticación de inicio de sesión SNMP que puede permitir a un atacante ejecutar código remotamente."}],"metrics":{"cvssMetricV30":[{"source":"nvd@nist.gov","type":"Primary","cvssData":{"version":"3.0","vectorString":"CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H","baseScore":10.0,"baseSeverity":"CRITICAL","attackVector":"NETWORK","attackComplexity":"LOW","privilegesRequired":"NONE","userInteraction":"NONE","scope":"CHANGED","confidentialityImpact":"HIGH","integrityImpact":"HIGH","availabilityImpact":"HIGH"},"exploitabilityScore":3.9,"impactScore":6.0}],"cvssMetricV2":[{"source":"nvd@nist.gov","type":"Primary","cvssData":{"version":"2.0","vectorString":"AV:N/AC:L/Au:N/C:P/I:P/A:P","baseScore":7.5,"accessVector":"NETWORK","accessComplexity":"LOW","authentication":"NONE","confidentialityImpact":"PARTIAL","integrityImpact":"PARTIAL","availabilityImpact":"PARTIAL"},"baseSeverity":"HIGH","exploitabilityScore":10.0,"impactScore":6.4,"acInsufInfo":false,"obtainAllPrivilege":false,"obtainUserPrivilege":false,"obtainOtherPrivilege":false,"userInteractionRequired":false}]},"weaknesses":[{"source":"nvd@nist.gov","type":"Primary","description":[{"lang":"en","value":"CWE-119"}]}],"configurations":[{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:schneider-electric:connexium_firmware:-:*:*:*:*:*:*:*","matchCriteriaId":"D0393FFB-DB2B-4C4E-95F2-CA1211467964"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:tcsefec23f3f20:-:*:*:*:*:*:*:*","matchCriteriaId":"98AE5D38-8266-4E4A-B52F-9CBEB022DD74"},{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:tcsefec23f3f21:-:*:*:*:*:*:*:*","matchCriteriaId":"9E89FA24-0128-4DF4-BFFF-0FD2C8E0386F"},{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:tcsefec23fcf20:-:*:*:*:*:*:*:*","matchCriteriaId":"7920453C-8B00-4E88-AB28-F051CEC2D0BA"},{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:tcsefec23fcf21:-:*:*:*:*:*:*:*","matchCriteriaId":"AE3371CC-A330-4777-887A-2ED11FE1A039"},{"vulnerable":false,"criteria":"cpe:2.3:h:schneider-electric:tcsefec2cf3f20:-:*:*:*:*:*:*:*","matchCriteriaId":"2BFDA3E0-E594-413D-98CB-5409FDBE60E4"}]}]}],"references":[{"url":"http://www.securityfocus.com/bid/94062","source":"ics-cert@hq.dhs.gov","tags":["Third Party Advisory","VDB Entry"]},{"url":"https://ics-cert.us-cert.gov/advisories/ICSA-16-306-01","source":"ics-cert@hq.dhs.gov","tags":["Third Party Advisory","US Government Resource"]},{"url":"http://www.securityfocus.com/bid/94062","source":"af854a3a-2127-422b-91ae-364da2661108","tags":["Third Party Advisory","VDB Entry"]},{"url":"https://ics-cert.us-cert.gov/advisories/ICSA-16-306-01","source":"af854a3a-2127-422b-91ae-364da2661108","tags":["Third Party Advisory","US Government Resource"]}]}}]}