{"resultsPerPage":1,"startIndex":0,"totalResults":1,"format":"NVD_CVE","version":"2.0","timestamp":"2026-04-15T17:24:24.936571400Z","vulnerabilities":[{"cve":{"id":"CVE-2011-20001","sourceIdentifier":"productcert@siemens.com","published":"2025-10-14T10:15:32.457","lastModified":"2026-04-15T00:35:42.020","vulnStatus":"Deferred","cveTags":[],"descriptions":[{"lang":"en","value":"A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.3), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.3). The web server interface of affected devices improperly processes incoming malformed HTTP traffic at high rate. This could allow an unauthenticated remote attacker to force the device entering the stop/defect state, thus creating a denial of service condition."}],"metrics":{"cvssMetricV40":[{"source":"productcert@siemens.com","type":"Secondary","cvssData":{"version":"4.0","vectorString":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X","baseScore":8.7,"baseSeverity":"HIGH","attackVector":"NETWORK","attackComplexity":"LOW","attackRequirements":"NONE","privilegesRequired":"NONE","userInteraction":"NONE","vulnConfidentialityImpact":"NONE","vulnIntegrityImpact":"NONE","vulnAvailabilityImpact":"HIGH","subConfidentialityImpact":"NONE","subIntegrityImpact":"NONE","subAvailabilityImpact":"NONE","exploitMaturity":"NOT_DEFINED","confidentialityRequirement":"NOT_DEFINED","integrityRequirement":"NOT_DEFINED","availabilityRequirement":"NOT_DEFINED","modifiedAttackVector":"NOT_DEFINED","modifiedAttackComplexity":"NOT_DEFINED","modifiedAttackRequirements":"NOT_DEFINED","modifiedPrivilegesRequired":"NOT_DEFINED","modifiedUserInteraction":"NOT_DEFINED","modifiedVulnConfidentialityImpact":"NOT_DEFINED","modifiedVulnIntegrityImpact":"NOT_DEFINED","modifiedVulnAvailabilityImpact":"NOT_DEFINED","modifiedSubConfidentialityImpact":"NOT_DEFINED","modifiedSubIntegrityImpact":"NOT_DEFINED","modifiedSubAvailabilityImpact":"NOT_DEFINED","Safety":"NOT_DEFINED","Automatable":"NOT_DEFINED","Recovery":"NOT_DEFINED","valueDensity":"NOT_DEFINED","vulnerabilityResponseEffort":"NOT_DEFINED","providerUrgency":"NOT_DEFINED"}}],"cvssMetricV31":[{"source":"productcert@siemens.com","type":"Secondary","cvssData":{"version":"3.1","vectorString":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","baseScore":7.5,"baseSeverity":"HIGH","attackVector":"NETWORK","attackComplexity":"LOW","privilegesRequired":"NONE","userInteraction":"NONE","scope":"UNCHANGED","confidentialityImpact":"NONE","integrityImpact":"NONE","availabilityImpact":"HIGH"},"exploitabilityScore":3.9,"impactScore":3.6}]},"weaknesses":[{"source":"productcert@siemens.com","type":"Secondary","description":[{"lang":"en","value":"CWE-20"}]}],"references":[{"url":"https://cert-portal.siemens.com/productcert/html/ssa-625789.html","source":"productcert@siemens.com"}]}}]}